YF3002 Fire Alarm Control Panel 2 Zone

Features:

  • Integrated circuit indicators

Each circuit has LED indicators for fire, circuit break, and short circuit.

  • Stand-by Battery Protection System

The system also monitors built-in battery overcharging to ensure the panel functions well before and during disaster.

  • Voltage source error detection

Whenever a voltage error is detected by the system, an alarm will alert and Changer Fault indicator will light to point out the problem.

Compare
Category:

Description

Prevent sending false alarms through TYY YF-3 2 Zone Fire Alarm Control Panel complete with a two-stage alarm delay function. The first signal that is sent will be reset and the panel will enter 8 seconds standby. At the second stage, if another signal is detected within 9 to 40 seconds, the panel will finally alert the fire alarms.

 

Category Conventional Fire Alarm Control Panel
Type Wall-mount
Power Source 230V AC 50/60 HZ ±10%
Standby Battery 24V DC
Charging Voltage Below 26V DC 450mA, trickle charging
Circuit Voltage  24V DC operation voltage under 10~11V DC 32mA
Rated Impedance Below 50Ω
Detector Connection No limitation for Conventional Rate of Rise or Fixed  Temperature Heat Detectors; Up to 30 Photoelectric Smoke Detectors can be  connected per zone (monitor current for detectors: 24V  DC 40μA )
E.O.L. Resistor 10KΩ
No. of Indicators The same as the number of zones (LED indicator  lamp)
No. of Bells The same as the number of zones
Color Red
Buttons Push-button
Cabinet Material Flame retardant ABS enclosure (up to 24L only)
Main Audio Mono tone sounder (above 85 dB for 1m distance)
Alarm Relay Contact No-voltage NO contact; capacity 250V AC/7A